In the hanging system, or “bota,” the panel is machined into trays that are hung from brackets attached to the studs. Concealed fastening, horizontal or vertical modularity, and large trays with stiffeners.
Hanging Tray
In the hanging or “boot” system, each piece of composite panel becomes a tray: the perimeter flanges are milled and folded, and notches (the “boots”) are cut into the vertical edges so the tray can hang from brackets clipped onto the rails. A screw through the top flange holds it in place, and all you see on the facade is the joint between trays.
It is the system of choice for tall trays and for facades with a vertical or horizontal layout. Installation runs from the bottom up and is quick: hang, level and screw, and each tray can later be unhooked for repairs or to reach building services. At StarModul we fabricate the trays in our workshop with CNC cutting and milling, formed corners, hanging reinforcements and, on large pieces, stiffeners sized to the wind calculation, and ship them numbered and ready to hang.
Concealed mounting
In the hanging system, or “boot” system, the composite panel is machined into trays: the perimeter flanges are milled and folded, and notches (the “boots”) are cut into the vertical edges. Each tray is hung from brackets clipped onto the studs and secured at the top with a screw. No fasteners are visible.
Components
Aluminum or stainless steel L-shaped spacers anchored to the wall; optional insulating shims to break the thermal bridge.
Vertical aluminum profiles in a T or omega shape at the joints, and in an L shape at intermediate points.
They clip onto the upright for adjustment and are secured with two self-tapping screws.
40- or 45-mm flanges, corners formed with riveted plates, and reinforcements on each boot.
Vertical members (glued and riveted on the inside) or a horizontal profile: these allow for larger trays and wider spacing between uprights.
Secure the tray from below to the intermediate rails and help align it.
With a horizontal brace, the spacing between studs can be up to about 1,200 mm, depending on the site's wind load calculations.
Workshop
We perform all of this machining in our workshop: see composite panel machining.
Construction details
System Specifications
| Element | Detail |
|---|---|
| Spacers | 6063 T5 aluminum double-T profile available in 14 lengths (from 59 to 254 mm, in 15-mm increments) or in a U-shape. Optional insulating spacer between the spacer and the wall to break the thermal bridge. |
| Separator–Upright Joint | M6 × 60/70 mm through-bolt, with 15 mm of adjustment for plumb alignment. |
| Stiles | 6063 T5 aluminum omega profile. First and last fasteners must be no more than 250 mm from the ends of the profile. |
| Hanging bracket | Extruded 6063 T5 aluminum part with an EPDM gasket to dampen vibrations (wind, traffic). It clips onto the omega bracket, slides up or down to the boot position, and is secured with self-tapping screws. |
| Tray with a 45 mm flange | Corners reinforced with 28 × 33 × 2 mm 1050 H24 aluminum angle stock and rivets. The long flange extends further into the omega profile and channels water more effectively. |
| Tray with a 40 mm flange | Each boot has a 2-mm aluminum hanging reinforcement. It uses less panel material for the flanges. |
| Top Mounting | Screws or rivets through the through holes in the upper flange, against the wings of the omega. |
| Forming Rivets | 4.8 × 15 mm blind rivet, aluminum/stainless steel. |
| Stiffeners | Angled composite profile glued (double-sided tape + adhesive) and riveted to the flanges. Six sizes depending on the length of the tray: < 750 · 750–1,500 · 1,500–2,400 · 2,400–4,000 · 4,000–5,000 · > 5,000 mm. |
| Distance from wall to panel face | From 100 to 310 mm, depending on the spacer. |
| Assembly Order | From bottom to top. |
The spacer is selected based on the insulation thickness and the wall's camber, always leaving a 30-mm air gap:
| Spacer (mm) | 59 | 74 | 89 | 104 | 119 | 149 | 179 | 209 | 254 |
|---|---|---|---|---|---|---|---|---|---|
| Insulation (mm) | 30 | 50 | 60 | 80 | 100 | 120 | 160 | 180 | 230 |
Frequently asked questions
It depends on the slab width, wind conditions, and stiffeners. Slabs taller than 700 mm are typical for this system; for larger sizes, stiffeners are added as calculated.